Air-insulated
State of the artsafe slide-in technology
Switch cells metal encapsulated / sealed
Single / double busbars
controlled pressure relief
The WATswitch.mv impresses with its space-saving and compactly designed cell design and is therefore a very good alternative to gas-insulated medium-voltage switchgear.
Manufacturer Neutral
A wide range of devices is available for selection and can be varied at will.Various well-known device manufacturers such as Siemens, ABB, Eaton, Schneider, Tavrida, Ritz, Zelisko, etc. can be used for circuit breakers, protection, earthing switches, converters, etc.
Switchgear cabinet design
Reliable and safe to operateHighest personal and system protection through arc fault testing IAC AFRL 40kA/1s Tested according to international standards IEC 62271-200 / VDE 0671-200
WATswitch.mv
Highlights WATswitch.mvVisible position of the switchgear
Simple check for voltage-free
operation
Contact and switching error protection by shutter
Secure viewing window
Rated voltage | 7,2 kV | 12 kV | 17,5 kV | 24 kV |
---|---|---|---|---|
Rated frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Lightning-Impulse withstand voltage | 60 kV | 75 kV | 95 kV | 125 kV |
Withstand voltage | 20 kV | 28 kV | 38 kV | 50 kV |
Withstand voltage | 20 kV | 28 kV | 38 kV | 50 kV |
Rated current busbar up to | 3150 A | 3150 A | 3150 A | 2500 A |
Rated short-time withstand up to | 40 kA | 40 kA | 40 kA | 25 kA |
Rated short-circuit duration up to | 3/4 s | 3/4 s | 3/4 s | 3/4 s |
Rated surge current up to | 104 kA | 104 kA | 104 kA | 63 kA |
Arc fault test 1s | 40 kA | 40 kA | 40 kA | 25 kA |
Degree of accessibility IAC | A FLR | A FLR | A FLR | A FLR |
Bulkhead class metal-clad | PM | PM | PM | PM |
Operational availability | LSC 2B | LSC 2B | LSC 2B | LSC 2B |
Degree of protection for ventilation / general | IP3X/4X | IP3X/4X | IP3X/4X | IP3X/4X |